Effect of coordination of optimal reclosing and fuzzy controlled braking resistor on transient stability during unsuccessful reclosing
Abstract
This paper analyzes the effect of the coordination of optimal reclosing and fuzzy logic-controlled braking resistor on the transient stability of a multimachine power system in case of an unsuccessful reclosing of circuit breakers. The transient stability performance of the coordinated operation of optimal reclosing and fuzzy controlled braking resistor is compared to that of the coordinated operation of conventional auto-reclosing and fuzzy controlled braking resistor. The effectiveness of the proposed method is confirmed by simulations in case of a nine-bus power system model as well as a ten-machine system. Simulation results of both balanced and unbalanced faults at different points in the power systems show that the coordinated operation of optimal reclosing and fuzzy controlled braking resistor is able to stabilize the systems well in case of an unsuccessful reclosing. Moreover, the transient stability performance of the coordinated operation of optimal reclosing and fuzzy controlled braking resistor is better than that of the coordinated operation of conventional auto-reclosing and fuzzy controlled braking resistor. © 2006 IEEE.
Publication Title
IEEE Transactions on Power Systems
Recommended Citation
Ali, M., Murata, T., & Tamura, J. (2006). Effect of coordination of optimal reclosing and fuzzy controlled braking resistor on transient stability during unsuccessful reclosing. IEEE Transactions on Power Systems (3), 1321-1330. https://doi.org/10.1109/TPWRS.2006.876670